Model | KRYP-15W KRYP-15 | KRYP-25W KRYP-25 | KRYP-38W | KRYP-60W |
Temp Range | -40℃~135℃ | -40℃~135℃ | -40℃~135℃ | -40℃~135℃ |
Tank volume | 60L | 100L | 200L | 300L |
heating power | 15kW | 25kW | 38kW | 60kW |
Refrigerating Output | 135℃ | 15kW | 25kW | 38kW | 60kW |
20℃ | 15kW | 25kW | 38kW | 60kW |
0℃ | 15kW | 25kW | 38kW | 60kW |
-20℃ | 10kW | 16kW | 26kW | 37kW |
-35℃ | 4kW | 6.5kW | 10kW | 15kW |
Temperature Control Accuracy | ±0.3℃ |
System pressure display | Pressure of Refrigeration system is realized by pressure gauge (High pressure, low pressure); |
The circulation system pressure is displayed on the touch screen by pressure sensor detection. |
Controler | Siemens PLC and Fuzzy-PID Control Algorithm |
Communicating Protocol | Ethernet Interface TCP/IP Protocol |
Internal Temp Feedback | Equipment tank internal temperature, refrigeration system condensation temperature, compressor suction temperature, cooling water temperature (water cooling equipment is configured)。 |
Heat | The maximum heating output power of the system (according to each model); |
The heater has triple protection and independent temperature limiter to ensure the safety of heating system; |
Heating power 10kW adopts regulator, heating power output control adopts 4~20mA linear control. |
Refrigerating Capacity | Refers to the ability to take away heat at different temperatures (ideal condition), the actual working conditions need to consider environmental heat dissipation, please enlarge properly, and do a good job of insulation measures. |
High temperature cooling module | It is possible to cool the module from a high temperature of 150℃ |
Circulating pump flow max | Adopt crown submagnetic drive pump / German brand magnetic drive pump |
110L/MIN 2.5BAR | 150L/MIN 2.5BAR | 200L/MIN 2.5BAR | 300L/MIN 2.5BAR |
Source 380V50HZ | 24kW max | 38kW max | 58kW max | 95kW max |
Shape Size (Air-cooled) | 800*1200*1850 | 1000*1500*1850 | | |
Shape Size (Water cooled) | 800*1200*1850 | 1000*1500*1850 | 1000*1500*1850 | 1450*2050*2050 |
Compression Engine | Emerson Valley Wheel / Turin, Italy |
Evaporimeter | Adopting DANFOSS Plate Heat Exchanger / High strength Plate Heat Exchanger |
Refrigeration Accessory | Emerson / Danfoss brand dry filter, pressure control, oil separator, etc. |
Expansion Valve | Danfoss thermostatic expansion valve/ Emerson electronic expansion valve |
Operation Panel | 7-inch color touch screen, and the temperature curve shows the export of EXCEL data |
Safe Guarding | With self-diagnosis function; phase sequence phase breaker, freezer overload protection; high-voltage pressure switch, overload relay, thermal protection device and other safety protection functions. |
Cryogen | R-404A/R507C |
Electronic pump interface | DN50 PN10 RF | DN65 PN10 RF | DN80 PN10 RF | DN100 PN10 RF |
Water-cooled type W | Type W is water cooled |
Water-cooled Condenser | Double-pipe (heat) exchanger |
Cooling Water 32℃ | 7m³/H | 12m³/H | 17m³/H | 24m³/H |
Shell material | Cold rolled sheet spray (Standard Colour 7035) |
Temperature spread | -40℃~150℃ |