Keyword Recirculating Chiller Ultra-low Temp Chillers SUNDI series TES series Products

cooling distribution unitsZLFQ-200  (+5℃ ~ +35℃) cooling distribution unit cdu

ZLFQ (+5℃ ~ +35℃)

  • Temperature Range+5℃ ~ +35℃
  • Temperature Control Accuracy± 0.5℃
  • Cooling Capacity200 ~ 500KW
  • Flow15 ~ 70m³/h
  • Place of OriginChina
  • Quality Guarantee Period12 months

Product Details

Liquid cooling equipment is suitable for semiconductor testing, electronic equipment constant temperature testing, cooling server supporting infrastructure, and other fluid temperature control places.

Advantages

  • The heating method within 40 ℃ is heated by compressor hot air.
  • The circulation system adopts a fully closed design, and the circulation pump adopts a magnetic drive pump.
  • 100% helium detection, 100% safety inspection to ensure the safety
    and reliability of the system.
  • 100% continuous operation of copy machine after 24 hours.
  • Condenser Micro-channel heat exchanger (air-cooled), plate heat exchanger (water-cooled)
  • Evaporator: plate heat exchanger
  • Throttling device: electronic expansion valve
  • Control system: PLC programmable controller
  • Communication: RS485 interface Modbus RTU protocol, Ethernet interface TCP/IP protocol
  • Operation interface: Wuxi Guanya customized 7-inch color touch screen, temperature curve display\EXCEL data export
  • Circulation system: The whole system is a fully closed system, low temperature does not absorb moisture in the air, does not volatilize heat transfer medium, low temperature automatically replenishes heat transfer medium into the circulation system.
  • Shell material: cold-rolled plate spray RAL7035
  • The inside of the pipeline contains: stainless steel SUS304, copper, ceramics, silicon carbide, silicone sealant, PTFE.

coolant distribution units

Request A Quote
*
*
*
loading!
Submitted successfully!
Submit failed! Demo is not allowed to be submitted, please forgive me!
Mailbox error!
Phone error!

 

ModelZLFQ-200ZLFQ-250ZLFQ-300ZLFQ-400ZLFQ-500
Temp range +5℃~35℃
Temp accuracy±0.5℃
Flow control15~30m³/h20~35m³/h25~40m³/h30~60m³/h40~70m³/h
 Flow control is adjusted by frequency converter
Cooling capacity(MAX) 200kW250kW300kW400kW500kW
 
Storage volume250L300L600L1000L1200L
Cooling SystemThe plant service water exchanges heat with the brine, and the brine provides cooling capacity for the heating equipment
MediumWater, silicone oil, fluorinated liquid, ethylene glycol aqueous solution, etc.
controllerPLC, fuzzy PID control algorithm, with cascade control algorithm
temperature controlHeat transfer medium outlet temperature control mode式
letter of agreementEthernet interface TCP/IP protocol
 RS485 interface modbus RTU protocol
Device Internal Temperature FeedbackEquipment heat transfer medium outlet temperature, medium inlet temperature, cooling water temperature
tank levelPressure sensor real-time monitoring
Medium pipelineSUS304
System pressureUsing the pressure sensor to detect and display on the touch screen
Heat ExchangerPlate heat exchanger, special attention: need to use clean factory water
operation panelWuxi Guanya customized 7-inch color touch screen, temperature curve display\EXCEL data export
SecurityWith self-diagnosis function; phase sequence and phase failure protector; pressure protection, overload relay, thermal protection device and other safety protection functions.
In and out interface sizeDN65DN65DN65DN80DN80
Cooling water interfaceDN80DN80DN100DN100DN125
cooling methodWater-cooled, the factory water temperature is lower than the minimum temperature provided by the equipment by more than 3°C, and the water temperature fluctuation is ≤3°C
Cooling water flow 7~20℃34m³/h43m³/h51m³/h69m³/h86m³/h
Power supply 380V 50HZ7kW7kW8kW9kW13kW
shellCold-rolled sheet spray RAL7035